Tech Forum | Login, New Customer? Register
        


Powerware 5115 UPS
Battery Run Time Chart


Powerware UPS

5115 500VA
5115 750VA
5115 1000VA
5115 1400VA

Battery Run time Chart
This guide provides typical application information. Battery run times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.
Powerware 5115 UPS - Battery Run Times (in minutes)
Load 500 UPS 750 UPS 1000 UPS 1400 UPS
200VA/128W 17 38 41 58
300VA/192W 11 27 28 41
500VA/320W 5 14 15 28
600VA/402W   9 10 19
750VA/503W   6 8 14
900VA/603W     6 10
1000VA/670W     5 8
1200VA/804W       6
1400VA/938W       5